Building door and window airtight field test equipment
SYL-18 type
Keywords JG/T211-2007GB/T7106 door and window on-site measuring instrument, on-site door and window airtightness detector, airtightness detector, on-site door and window airtightness detector manufacturer,
one,
Building door and window airtight field test equipment
Overview
The building door and window field detector is a new portable door and window field detector developed by our company. Pick
Use the manual knob to adjust the air pressure, display the instrument cycle detection and display air pressure, air flow, deformation displacement and so on. The wind source and control adjustment system are integrated into a suitcase, which is small in size, light in weight, easy to carry, reliable and durable, and easy to use.
two,
Building door and window airtight field test equipment
Applicable standard
JG/T211-2007 "On-site inspection method for airtight, watertight and wind pressure resistance of building exterior windows" and GB/-T7106, 7 and 8 standards.
three,
Building door and window airtight field test equipment
Main Specifications
1, the power supply voltage: AC220V
2. Power: 7.2kW
3, airtight pressure: ± 200Pa
4, watertight pressure: 0 ~ +700Pa
5, wind pressure: ± 2000Pa
6, air flow: 20m / s (267.8 cubic meters / hour)
four.
Building door and window airtight field test equipment
working environment
1, relative humidity: ≤ 85%, no condensation;
2, temperature: 0 ~ 50 ° C;
3. Altitude: <1500 meters;
Fives.
Building door and window airtight field test equipment
Display the correspondence between the channel number of the table and the detected amount
Channel number is measured
CHl ±200Pa pressure
CH2 air flow 0~267.8 m/h (flow rate 20m/s)
CH3 ± 6000Pa pressure (actual value = display value xl0)
CH4,5,6 three-point displacement display, 0~20mm
six.
Building door and window airtight field test equipment
Steps
1. Install the static pressure box, air path and waterway system:
2. Open the suitcase and insert the straight pipe section of the wind pipe into the positive pressure port.
3. Insert the air flow meter into the straight pipe section and insert its cable plug into the flow socket on the suitcase:
4. Stick the plastic cloth on the outer window and put the hose into the plastic cloth and seal it with tape.
5. Insert the pressure tube into the controller and clamp it in the plastic cloth.
6. Close the air switch, turn on the power, and the airtight light is on;
7. Adjust the "Voltage" knob counterclockwise to the minimum;
Positive airtight 6-17
Pre-pressurization 6-10
8. Press the "Airtight" "Wind 1" button; if the wind is insufficient, the "Wind 2" button is also pressed;
9. Rotate the “Voltage†knob clockwise slowly, and watch the CH1 channel pressure value of the display table at 150 Pa (see the corresponding relationship between the channel number of the display table and the detection amount);
10. Press the "Wind l" button;
11. When the pressure returns to zero, press the "Wind 1" button again, after reaching 150Pa, stabilize for 3s, press the "Wind l" button again;
12. Repeat 9)-times to adjust the “Voltage†knob counterclockwise to the minimum:
Airtight detection 11-15
13. Press the "Wind l" button;
14, slowly rotate the "Voltage" knob clockwise, while watching the CH1 channel pressure value l00Pa of the display table, stabilize l0s;
15. Rotate the “Voltage†knob clockwise slowly, and watch the CH1 channel pressure value of the display table 150Pa, and stabilize l0s;
16. Slowly rotate the “Voltage†knob counterclockwise, and watch the CH1 channel pressure value l00Pa of the display table, and stabilize l0s:
17. Adjust the "Voltage" knob counterclockwise to the minimum;
Negative airtight
18. Insert the straight pipe section of the wind road into the negative pressure port and insert it tightly;
Pre-pressurization 17-20
19. Rotate the “Voltage†knob clockwise slowly, and watch the CH1 channel pressure value of the display table -150Pa (see the correspondence between the channel number of the display table and the detection amount);
20. Press the "Wind 1" button;
21. When the pressure returns to zero, press the "Wind 1" button again, after reaching -150Pa, stabilize for 3s, press the "Wind 1" button again;
22. Repeat 19) once, adjust the “Voltage†knob counterclockwise to the minimum;
Airtight detection 21) ~ 25)
23. Press the "Wind 1" button:
24, slowly rotate the "Voltage" knob clockwise, while watching the CHl channel pressure value of the display table. After -100Pa, stable l0s;
25, slowly rotate the "Voltage" knob clockwise, while watching the CH1 channel pressure value of the display table -150Pa, stabilize l0s;
26, slowly rotate the "Voltage" knob counterclockwise, while watching the CH1 channel pressure value of the display table - l00Pa, stabilize l0s;
27. Adjust the “Voltage†knob counterclockwise to the minimum;
Watertight detection
28. Insert the straight pipe section of the wind road into the positive pressure port and insert it tightly;
29. Press the Wind 1 button:
30. Rotate the “Voltage†knob clockwise and watch the CH2 channel pressure value of the display table at 500Pa. After 3s stabilization, press the “Wind 1†button:
31. Press the “Wind 1†button again, and wait for CH2=500Pa to stabilize for 3s;
32. Repeat 28)- times, press the "Wind 1" button;
33. Open the water spray system, adjust the water flow rate 2L/min.m2, and start spraying;
Stable pressure detection 31-32
34. After spraying for 5 minutes, press the “Wind 1†button again, and slowly rotate the “Voltage†knob clockwise, and watch the CH2 channel pressure value I00Pa of the display table, after 5m stabilization;
35. Continue to increase to 700Pa according to the stable step-by-step pressurization method, stabilize 5m, and complete stable pressure detection;
Design value pressure detection 34-35
36. After spraying for 5 minutes, press the “Wind 1†button again, and slowly rotate the “Voltage†clockwise.
Knob, while watching the pressure value of the CH2 channel pressure value of the display meter, after 15m stabilization,
Complete design value pressurization detection.
37. Adjust the “Voltage†knob counterclockwise to the minimum, press the “Wind l†button;
Anti-wind pressure detection 36-59
Preparing for pressurization 36-4)
38. Insert the straight pipe section of the wind road into the positive pressure port and insert it tightly:
39. Rotate the “Voltage†knob clockwise slowly, and watch the CH2 channel pressure value of the display table at 500 Pa (the correspondence between the channel number of the display table and the detection amount);
40. Press the "Wind l" button;
41. When the pressure returns to zero, press the “Wind 1†button again: After reaching 500Pa, stabilize for 3s, press F “Wind 1†button again;
42. Repeat 39)-times, adjust the “Voltage†knob counterclockwise to the minimum;
Positive deformation detection 41-47
43. Press the "Wind 1" button;
44. Rotate the “Voltage†knob clockwise slowly, and watch the CH2 channel pressure value of the display table after 200Pa, stabilize l0s, record the CH4, 5, 6 displacement values ​​and calculate the deflection B, B≥1/300, execute 47 );
45. Rotate the “Voltage†knob clockwise slowly, and watch the CH2 channel pressure value of the display table after 400Pa, stabilize l0s, record the CH4, 5, 6 displacement values ​​and calculate the deflection B, B≥l/300, execute 47
46. ​​Rotate the <pressure adjustment knob counterclockwise slowly, and watch the CH2 channel pressure value of the display table at 1800Pa, stabilize l0s, record the CH4, 5, 6 displacement values ​​and calculate the deflection B, B≥l/300, execute 47
47. Rotate the “Voltage†knob counterclockwise slowly, and watch the CH2 channel pressure value 2000Pa of the display table, stabilize l0s, record the CH4, 5, 6 displacement values ​​and calculate the deflection B, B≥l/300, execute 47
48. Adjust the “Voltage†knob counterclockwise to the minimum;
Negative preparation pressure 48-52
49. Insert the straight pipe section of the wind road into the negative pressure port and insert it tightly:
50. Rotate the “Voltage†knob clockwise slowly, and watch the CH2 channel pressure value of the display meter –500Pa (the correspondence between the channel number of the display table and the detection amount);
51. Press the "Wind 1" button:
52. When the pressure returns to zero, press the “Airtight†button again, after reaching -500Pa, stabilize for 3s, press the “Airtight†button again;
53. Repeat 51 times, adjust the “Voltage†knob counterclockwise to the minimum;
Negative positive deformation detection 53-59
54. Press the "Wind l" button;
55. Rotate the “Voltage†knob clockwise slowly, and watch the CH2 channel pressure value of the display table -200Pa, stabilize l0s, record the CH4,5,6 displacement values ​​and calculate the deflection B, B≥-l/300. Execution 59
56. Rotate the “Voltage†knob clockwise slowly, and watch the CH2 channel pressure value of the display table -400Pa, stabilize l0s, record the CH4,5,6 displacement values ​​and calculate the deflection B, B≥-1/300. Execution 59
57. Rotate the “Voltage Control†knob counterclockwise, and watch the CH2 channel pressure value of the display table -1800Pa, stabilize l0s, record the CH4,5,6 displacement values ​​and calculate the deflection B, B≥-1/300. Execution 59
58. Slowly rotate the "Voltage" knob counterclockwise. At the same time, after watching the CH2 channel pressure value of the display table -2000Pa, stabilize l0s, record the CH4,5,6 displacement values ​​and calculate the deflection B, B≥-l/300, execute 59
59. Adjust the “Voltage Control†knob counterclockwise to the minimum;
End detection 60-62
60. Adjust the “Voltage†knob counterclockwise to the minimum;
61. Press F "Wind 1" and "Wind 2" button;
62) Turn off the air switch, disconnect the power supply, and the power indicator is off.
Building door and window airtight field test equipment
Precautions
1. When the air flow meter is inserted into the straight pipe section, the direction is adjusted correctly;
2. In order to ensure safety, a reliable grounding wire should be connected to the detector at the site;
3. All units of measurement should be converted to the unit of measurement required by the standard, which is convenient for the judgment level.